Механизм управления с пружинным накопителями энергии обеспечивает быстрое закрытие и переключение (<1000 мс).
Место оператора: Местный/Удаленный.
11KV LBS оснащен электронным контроллером, этоВыключатель нагрузки sf6Может работать локально или с интерфейсом FTU/RTU для работы с консолью.
The type of high-voltage bypass type SF6 11KV LBS insulated load switch is divided into manual type and electric type, which is an engineering bypass type load switch used for the maintenance and construction of power distribution cabinet in order to make uninterrupted power supply to distribution lines. This 11kv load break switch utilizes SF6 gas, known for its outstanding insulation and arc extinguishing performance. Inquiry 11kv load break switch price. Check more pole top switches.
Parameter Name | Unit | Technical Requirement |
Rated Maximum Voltage | kV | 12 |
Rated continuous Current | A | 630 |
Short Time Withstand Current | kA | 20 |
Short-circuit Making Current (peak) | kA | 50 |
Power Operating Time (Close/Open) | sec | <2 |
Mechanical Operations | times | 3000 |
Rated full load operations | times | 400 |
Breaking Capacity | ||
Main Active (0.7pf) | A | 630 |
Cable charging | A | 5 |
Transformer magnetizing | A | 10 |
Lightning Impulse Withstand Level | ||
Phase to Earth | kV | 75 |
Across interrupter | kV | 85 |
Power Frequency withstand voltage | ||
Phase to Earth | kV | 42 |
Across interrupter | kV | 50 |
Other Ratings & Specifications | ||
Creepage Distance (Silicon) | mm | 830 |
IP Level | 65 | |
Arc Extinction Medium | SF6 Gas | |
Insulation Medium | SF6 Gas | |
Leakage Rate | cc/ sec | ≤0.5% |
Product size (max) | ||
Width | mm/in | 1368/54 |
Height | mm/in | 530/21 |
Environmental conditions for equipment use |
height above sea level:≤3000m |
Air temperature: -40℃~+50℃ |
Maximum diurnal temperature difference:≤25℃ |
Relative humidity:Daily mean95% monthly average90% |
Maximum wind speed:≤34m/s |
Earthquake intensity:<8 degree |
Icing thickness: <10mm |
Thickness of snow: <35mm |
irradiance: <0.1W/cm2 |
Pollution grade: Ⅲ class, Ⅳ class Ⅲ, Ⅳ |
Installation site: No fire disaster, explosion danger, chemical corrosion, and frequent strenuous vibration places |
The 11KV LBS load switch that uses SF6 gas as insulation and arc extinguishing medium is called the SF6 gas load break switch. It can be used to switch and switch load current and overload current, and it can also be used to switch and switch no-load circuits, no-load transformers, and capacitors and outdoor pole mounted load break switch groups, among others. All three-position load switches with the functions of connecting, disconnecting, and grounding have the characteristics of simple structure and low price. But the load switch cannot disconnect the short-circuit current.
The 11KV LBS SF6 load switch is an excellent load switch that many users have experienced in recent years. In addition to its long electrical life and strong braking force, it has the same advantages as the vacuum load switch. Its outstanding advantage is that it is easy to achieve three working positions (connected, disconnection and grounding), small current (inductance, capacitance) breaking, strong resistance to severe environmental conditions. It is suitable for popularization and application in urban and rural medium voltage distribution networks.
Сопутствующие товары
Контакт Нас
Начните свое партнерство с Gopower